Control Connections; Assignment Of The Control Terminal Strip X2A; Assignment Of Socket X2B - KEB combivert R6-S Instruction Manual

Power supply and regeneration unit
Hide thumbs Also See for combivert R6-S:
Table of Contents

Advertisement

Connection of the Control Board
4.5

Control connections

4.5.1 Assignment of the control terminal strip X2A

PIN Function
10
24...30 V input
11
Common
12
Enable
13
Reset
14
Programmable Input
15
External Fault
16
Digital in-/output
17
24 V-output
18
Common
19
Digital output 1
20
Ready (No fault)
21
Analog output
22
24 V-output
23
Mass
24
Relay 1 / NO contact
25
Relay 1 / NC contact
26
Relay 1 / switching
contact
27
Relay 2 / NO contact
28
Relay 2 / NC contact
29
Relay 2 / switching
contact

4.5.2 Assignment of socket X2B

RJ45 socket for phase synchronization and
temperature sensor
The connection is made with a shielded industrial ethernet patch cable 1:1 with the socket X2B on the commutation
choke.
US - 24
X2A
Tightening torque 0.5 Nm
Name
Description
Vin
External supply of the control board
COM
Reference potential
ST
Enables the unit for operation
I1
Resets at the falling edge of a pulse
I2
Prog. function for advanced use
I3
Prog. function for advanced use (E.EF)
I/O
Active signal (connection for all R6
at parallel operation in master - slave
applications)
Vout
Voltage supply for in- and outputs
COM
Reference potential
O1
Transistor output
O2
Transistor output
ANOUT
-
Vout
see terminal 17
COM
Reference potential
RLA
RLB
Relay output (RDY - Ready no Fault)
RLC
FLA
Relay output (CCC - Charge Contactor
FLB
Control)
FLC
No.
Name
1
2
3
U13_syn Synchronization phase 1 / 3
4
5
U21_syn Synchronization phase 2 / 1
6
7
U32_syn Synchronization phase 3 / 2
8
Function
t1
Connection for temperature sensor
t2
reserved
reserved
reserved
Specifi cations
R
: 4.4 kΩ
in
24 V
/ max. 100 mA
+/-1
I
: 25 mA
max
I
: 25 mA
max
0...±10 V / max. 5 mA
30 V DC
0.01...2 A
125VAC
0.01...2 A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents