Danfoss VLT HVAC Design Manual page 160

Hide thumbs Also See for VLT HVAC:
Table of Contents

Advertisement

8 General Specifications and Troubleshooting
8.1.1 Mains Supply High Power
Mains Supply 3 x 380 - 480 VAC
Typical Shaft output at
400 V [kW]
Typical Shaft output at
460 V [HP]
Enclosure IP21
Enclosure IP54
Enclosure IP00
Output current
Continuous
(at 400 V) [A]
Intermittent (60 sec
overload)
(at 400 V) [A]
Continuous
(at 460/ 480 V) [A]
Intermittent (60 sec
overload)
(at 460/ 480 V) [A]
Continuous KVA
(at 400 V) [KVA]
Continuous KVA
(at 460 V) [KVA]
Max. input current
8
Continuous
(at 400 V ) [A]
Continuous
(at 460/ 480 V) [A]
Max. cable size, mains
motor, brake and load
share [mm
Max. external pre-
fuses [A]
Estimated power loss
at rated max. load [W]
4)
Estimated power loss
at rated max. load [W]
4)
Weight,
enclosure IP21, IP 54
[kg]
Weight,
enclosure IP00 [kg]
Efficiency
Output frequency
Heatsink overtemp.
trip
Power card ambient
trip
160
P110
110
150
D1
D1
D3
212
233
190
209
147
151
204
183
2 x 70
(2 x 2/0)
2
2)
(AWG
)]
300
1
3234
, 400 V
2947
, 460 V
96
82
4)
85 °C
MG.11.B9.02 - VLT
P132
P160
132
160
200
250
D1
D2
D1
D2
D3
D4
260
315
286
347
240
302
264
332
180
218
191
241
251
304
231
291
2 x 70
2 x 150
(2 x 2/0)
(2 x 300 mcm)
350
400
3782
4213
3665
4063
104
125
91
112
0.98
0 - 800 Hz
90 °C
105 °C
60 °C
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Design Guide
P200
P250
200
250
300
350
D2
D2
D2
D2
D4
D4
395
480
435
528
361
443
397
487
274
333
288
353
381
463
348
427
2 x 150
2 x 150
(2 x 300 mcm)
(2 x 300 mcm)
500
630
5119
5893
4652
5634
136
151
123
138
105 °C
115 °C

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT HVAC and is the answer not in the manual?

Table of Contents