7 RS-485 Installation and Set-up
7.1.3 Frequency converter hardware setup
Use the terminator dip switch on the main control board of the frequency
converter to terminate the RS-485 bus.
The factory setting for the dip switch is OFF.
7.1.4 Frequency Converter Parameter Settings for Modbus Communication
The following parameters apply to the RS-485 interface (FC-port):
Parameter
7
Number
8-30
8-31
8-32
8-33
8-35
8-36
8-37
7.1.5 EMC Precautions
The following EMC precautions are recommended in order to achieve interference-free operation of the RS-485 network.
NB!
Relevant national and local regulations, for example regarding protective earth connection, must be observed. The RS-485 communi-
cation cable must be kept away from motor and brake resistor cables to avoid coupling of high frequency noise from one cable to
another. Normally a distance of 200 mm (8 inches) is sufficient, but keeping the greatest possible distance between the cables is
generally recommended, especially where cables run in parallel over long distances. When crossing is unavoidable, the RS-485 cable
must cross motor and brake resistor cables at an angle of 90 degrees.
130
Parameter name
Function
Protocol
Select the application protocol to run on the RS-485 interface
Address
Set the node address. Note: The address range depends on the protocol se-
lected in par. 8-30
Baud Rate
Set the baud rate. Note: The default baud rate depends on the protocol se-
lected in par. 8-30
PC port parity/Stop bits
Set the parity and number of stop bits. Note: The default selection depends
on the protocol selected in par. 8-30
Min. response delay
Specify a minimum delay time between receiving a request and transmitting
a response. This can be used for overcoming modem turnaround delays.
Max. response delay
Specify a maximum delay time between transmitting a request and receiving
a response.
Max. inter-char delay
Specify a maximum delay time between two received bytes to ensure time-
out if transmission is interrupted.
MG.11.B9.02 - VLT
Illustration 7.3: Terminator Switch Factory Setting
Protocol
Protocol
Protocol
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Design Guide