6 Using the product
6.1.3.
18
Shop for Data Logging products online at:
✓ The valve actuators are closed.
1. Connect the refrigerant hoses for low-pressure side (blue) and
high-pressure side (red) to the measuring instrument.
2. Connect the refrigerant hoses to the system.
WARNING
The measuring instrument dropping down or any other comparable
mechanical load can cause breakage of the pipe pieces in the
refrigerant hoses. The valve actuators may also suffer damage,
which in turn could result in further damage inside the measuring
instrument, which may not be detectable from outside.
> For your own safety you should return the measuring
instrument to the Testo Service for technical inspection.
> You should therefore always replace the refrigerant hoses with
new ones after the measuring instrument has dropped down or
after any comparable mechanical loading.

Choosing the measuring mode

1. Press [Mode].
-
The configuration menu is opened.
2. Choose the measuring mode.
Key functions
Representation
[▲]
or
[▼]
[Ok]
[ESC]
Selectable functions
Pressure/Temperature
Tightness test
Evacuation
Charging
Emptying
Pressure/Compressor
Current
Efficiency calc.
See also Performing the measurement, page 19.
www.
Explanation
Select measuring mode
Enable measuring mode
Exit the menu