6 Using the product
6.2.5.
6.2.6.
22
Shop for Data Logging products online at:
Evacuation
The required pressure unit display must be set in the
testo 570.
In order to be able to use the readings from the testo
552 via the testo 570 in the EasyKool software, you
need EasyKool software version 4.0 or later.
(See testo 552 instruction manual.)
✓ The actions described in the chapter "Preparing for
measurement" have been performed.
✓ The desired units have been set.
See Making settings, page 13.
1. Press
[
].
2. Zero the measuring instrument at ambient pressure [p=0].
3. Press [Mode].
4. Select [Evacuation].
-
The evacuation view is displayed.
5. Start evacuation of the system.

Charging

✓ The actions described in the chapter "Preparing for
measurement" have been performed.
1. Press [Mode].
2. Select [Charging].
-
The charging view is opened.
3. Enter the value read on the refrigerant scales: Press [Change].
4. Adjust the flashing number with
and
[►]
to go to the next number.
5. Confirm the input with [OK].
6. Choose the memory location.
7. Press [Save].

Emptying

✓ The actions described in the chapter "Preparing for
measurement" have been performed.
1. Press [Mode].
2. Select [Emptying].
-
The emptying view is opened.
3. Enter the value read on the refrigerant scales: Press [Change].