8 - MENU ITEMS AND OPERATION
n - Maximum power (only for expert users)
It allows to set the maximum flame limit at which the boiler can operate to reach the set temperature target.
To change the power act as follows:
Press the "menu" button.
Scroll to "Settings" using the arrows
Press "menu" to confirm.
Scroll to "Maximum power" using the arrows.
Press "menu" to confirm.
Change the power from 01 to 05 with the + - keys
Press "menu" to confirm and "esc" to exit
o - Components test (only when the boiler is switched off)
It can only be carried out with the boiler switched off, it allows to select the components to be tested:
Spark plug: it is turned on for a fixed time of 1 minute during which the panel displays the countdown seconds.
Feed screw: it is powered for a fixed time of 1 minute during which the panel displays the countdown seconds.
Extractor: it is activated at 2500 rpm for a fixed time of 1 minute during which the panel displays the countdown seconds.
Exchanger: it allows to carry out the test in V5 for a fixed time of 1 minute during which the panel displays the countdown seconds.
Pump: it is activated for a fixed time of 10 seconds during which the panel displays the countdown.
3 way: the 3 way valve is activated for a fixed time of 1 minute during which the panel displays the countdown seconds.
To activate the "Components test" function (only when the boiler is switched off) act as follows:
Press the "menu" button.
Scroll to "Settings" using the arrows
Press "menu" to confirm.
Scroll to "Components test" using the arrows.
Press "menu" to confirm.
Select the test to be performed with the + - keys
Press "menu" to confirm and "esc" to exit
p - Chimney sweep function (for maintenance technicians only)
This function can be activated only when the boiler is on and with power output and heating operation power with parameters P5, with
fan (if present) in V5. Any loading/smoke ventilation percentage corrections must be taken into account. This status lasts 20 minutes, the
countdown is displayed on the panel. During this interval the thermostat/puffer/room set point/H
only the safety shutdown at 85°C remains active. At any time the technician can interrupt this stage by quickly pressing the on/off key.
To activate the "Chimney sweep" function act as follows:
Press the "menu" button.
Scroll to "Settings" using the arrows
Press "menu" to confirm.
Scroll to the "Chimney sweep" function using the arrows.
Press "menu" to confirm.
Select "On" with the + - keys (Off by default)
Press "menu" to confirm and "esc" to exit
Technical Dept. - All rights reserved - Reproduction is prohibited