Sonel MIC-2501 Operating Manual page 31

Insulation resistance meter
Table of Contents

Advertisement

Measurement of leakage current
Display range
0...ILmax
ILmax – maximum current at short circuit of leads,
resolution and units result from the measurement range of individual insulation resistance.
Low-voltage measurement of continuity of circuit and resistance
Measurement of continuity of protective conductors and equipotential bondings with 200 mA
current
Measuring range according to IEC 61557-4: 0.10 ...999 
Display range
0.00 ...19.99
20.0 ...199.9
200 ...999
Voltage at open terminals: 4 V...24 V
Output current at R < 2: I
Compensation of test leads resistance
Measurements for both current polarizations.
When the range is exceeded, the device displays "> 999 Ω" message
Other technical data
a) type of insulation .......................................................... double, acc. to EN 61010-1 and IEC 61557
b) measurement category .................................................... IV 600 V (III 1000 V) acc. to EN 61010-1
c) degree of housing protection acc. to EN 60529......................................................................... IP65
d) power supply of the meter................................................... SONEL battery pack, NiMH 9.6 V 2 Ah
e) Battery charging time .................................................................................... usually 4 h, max. 10 h
parameters of the external power supply adapter ................................ 90 V...264 V, 50 Hz...60 Hz
f)
g) dimensions .......................................................................................... 200 mm x 150 mm x 75 mm
h) meter weight ............................................................................................................. approx. 1.0 kg
allowable batter pack charging temperatures in mode 500mA ................................ +10 °C...+40 °C
i)
temperatures at which the charging process is interrupted ................................ <0 °C and ≥ +50 °C
j)
k) operating temperature range with external power supply adapter ...................... <0 °C and ≥ +50 °C
storage temperature ................................................................................................ -20 C...+60 C
l)
m) operating temperature ............................................................................................. -15 C...+40 C
n) humidity ....................................................................................................................... 20 %...90 %
o) reference temperature ...............................................................................................+23 C ± 2 C
p) reference humidity ....................................................................................................... 40 %...60 %
q) altitude (above sea level) .................................................................................................. <2000 m
r)
number of measurements R
s) modular ................................................................................................................................... LCD
t)
memory of measurement results ....................................................................................... 990 cells
u) data transmission .................................................................................................. USB connection
v) quality standard ... design, construction and manufacturing are ISO 9001, ISO 14001, PN-N-18001
compliant
w) the device meets the requirements of IEC 61557 standard
x) the product meets EMC requirements (immunity for industrial environment) according to the follow-
ing standards ................................................................. EN 61326-1:2013 and EN 61326-2-2:2013
Resolution
Resolution
0.01
0.1
> 200 mA
SC
acc. to PN-EN 61557-2 .................................................. approx. 800
ISO
OPERATING MANUAL MIC-2501 version 1.04
m, μ, n
1
Basic uncertainty
Calculated basing on re-
sistance measurements
Basic uncertainty
(2% m.v. + 3 digits)
(4% m.v. + 3 digits)
29