USER MANUAL INSULATION RESISTANCE METER MIC-10 ● MIC-30 SONEL S.A. Wokulskiego 11 58-100 Świdnica Poland Version 2.01 29.09.2022...
Page 4
Thank you for purchasing the MIC-10 / MIC-30 insulation tester. Please acquaint yourself with this manual to avoid measuring errors and prevent possible problems related to the operation of the meter. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
All other parts of the text relate to all types of the instrument. Safety MIC-10 / MIC-30 meter is designed for performing check tests of protection against electric shock in mains systems. The meter is used for making measurements and providing results to determine safety of electrical installations.
Each change DAR PI <-> Ab1Ab2 will set standard times t1, t2 and t3: - for PI and DAR t1=30s, t2=60s, t3=none, - for Ab1 and Ab2 t1=15s, t2=60s, t3=none. Description of a firmware update is presented in the chapter 6. MIC-10 / MIC-30 – USER MANUAL...
U , t1, t2, t3. buttons to change the parameter value. Press ENTER to confirm settings (confirmed by beep) or press ESC to leave without saving the changes. MIC-10 / MIC-30 – USER MANUAL...
Page 9
In order to maintain (lock) the measurement order to maintain the measurement, press ENTER while holding START - push-button pressed - the following symbol will be displayed . In order to interrupt the measurement, press ESC or START. MIC-10 / MIC-30 – USER MANUAL...
Page 10
Notes: During measurements of insulation resistance, dangerous voltage up to 1 kV occurs at the ends of test leads of MIC-10 / MIC-30 meter. It is forbidden to disconnect test leads before the measurement is completed. Failure to obey the above instruction will lead to high voltage electric shock and make it impossible to discharge the object tested.
Page 11
Leakage current too high (breakdown of insulation during the measurement.) Discharging of the object tested after the measurement. LED is lit The tested object is live. The measurement is blocked. in red, two-tone acoustic signal Discharged batteries (rechargeable batteries). MIC-10 / MIC-30 – USER MANUAL...
(position 50...1000V - selected with 10V step). The meter is in the voltage measurement mode. After inserting WS-04 into the socket, the screen displays a message indicating the detection of the adapter. MIC-10 / MIC-30 – USER MANUAL...
Page 13
, LIMIT I! the measurement is interrupted only for the current pair of leads and not for the entire measurement. - In case of error the entire measurement is interrupted. - Other comments and displayed symbols as for the double-lead measurement. MIC-10 / MIC-30 – USER MANUAL...
The meter is ready for measurement. Connect the meter to the object tested. The measurement starts automatically when the meter detects a resistance within the measurement range. The measurement may be also triggered manually by pressing START push-button. MIC-10 / MIC-30 – USER MANUAL...
Page 15
The measurement result may be affected by additional uncertainty. LED is lit The tested object is live. The measurement is blocked. in red, two-tone acoustic signal Resistance compensation completed for test leads compensation resistance taken into consideration when displaying result. MIC-10 / MIC-30 – USER MANUAL...
The meter is ready for measurement. Connect the meter to the object tested. The measurement is continuous. Read out the result. Note: - For R <30Ω there is a continuous beep and LED lights green. MIC-10 / MIC-30 – USER MANUAL...
In order to remove the compensation made (and return to default calibration), perform the above-mentioned activities with test leads open – messages disappear, the following message is displayed MIC-10 / MIC-30 – USER MANUAL...
When you go to the initial screen of a given function (e.g. by using ESC button), you can recall this result automatically after pressing ENTER. Similarly, you can view the latest measurement result after turning off and then turning on the meter (if the position of function selector has not been changed). MIC-10 / MIC-30 – USER MANUAL...
Memory of measurement result data MIC-10 / MIC-30 Meters are equipped with a memory for storing test results (990 cells, each of which may contain a set of measurements of R and R ). The whole memory is divided into 10 CONT memory banks with 99 cells in each bank.
Page 20
Press ENTER, to save the result in the memory or ESC to display the result without saving it. Saving is indicated by a triple beep and by a rectangle displayed on the main display field. MIC-10 / MIC-30 – USER MANUAL...
- While viewing R results, the field of timer / memory displays alternately bank and cell numbers and the time in which the result was entered into memory. This applies to all R and I measurements. MIC-10 / MIC-30 – USER MANUAL...
Set the bank number to be deleted acc. to section 4.2. St the cell number to “--”. The symbol appears which indicates the readiness to delete. Press ENTER . symbols appear, asking you to confirm deletion. MIC-10 / MIC-30 – USER MANUAL...
"01". 4.3.2 Deleting the whole memory Set the rotary switch of function selection at MEM position. St the bank number to “--”. The symbol appears which indicates the readiness to delete. MIC-10 / MIC-30 – USER MANUAL...
In order to ensure the communication of the meter with a computer, Bluetooth module is required with an additional software. A program that may be used for this purpose is Sonel Reader. It allows users to read and display the measurement data stored in the meter memory. This program may be downloaded free from the manufacturer's website: www.sonel.pl.
During the process of pairing the meter with a PC enter PIN code compatible with the PIN code of the meter defined in main settings. On the computer start data storing programme. Press ESC to exit the transmission mode. Standard pin for Bluetooth is "1234". MIC-10 / MIC-30 – USER MANUAL...
PIN code of an application must be compatible with the PIN code of the meter defined in main settings. Press ENTER to start the transmission. Press ESC to exit the transmission mode. Standard pin for OR-1 is "123". MIC-10 / MIC-30 – USER MANUAL...
- at that time all buttons are inactive. - After completing the update the meter is automatically switched off. - After switching on, the meter shortly displays the current number of internal software (firmware). MIC-10 / MIC-30 – USER MANUAL...
The meter switches off automatically. 7.2 Replacing battery/rechargeable batteries MIC-10 / MIC-30 Meters are powered by four AA alkaline LR6 batteries or rechargeable batteries of NiMH type. NOTE! Before removing the battery cover, disconnect the test leads. To replace the batteries/ rechargeable batteries: 1.
The casing of the meter may be cleaned with a soft, damp cloth using all-purpose detergents. Do not use any solvents or cleaning agents which might scratch the casing (powders, pastes, etc.). The electronic system of the meter does not require maintenance. MIC-10 / MIC-30 – USER MANUAL...
(3% m.v. + 8 digits) 1.000 to 9.999 M 0.001M 10.00 to 99.99M 0.01 M [ (5% m.v. + 8 digits)] * 100.0 to 500.0 M 0.1 M * - for WS-04 adapter MIC-10 / MIC-30 – USER MANUAL...
Page 31
= 1000V: 1000k to 10.00G Display range Resolution Accuracy for U = 1000V 0.0...999.9k 0.1k 1.000...9.999M 0.001M (3% m.v. + 8 digits) 10.00...99.99M 0.01M 100.0...999.9M 0.1M 1.000...9.999G 0.001G (4% m.v. + 6 digits) 10.00G 0.01G MIC-10 / MIC-30 – USER MANUAL...
Page 32
Voltage at open terminals: <8V Output current at R < 2: I > 200mA Compensation of test leads resistance Current flowing unidirectionally Current flowing bidirectionally, average resistance is displayed MIC-10 / MIC-30 – USER MANUAL...
EMC requirements (immunity for industrial environment) according to the following standards ..............................IEC 61326-1 and IEC 61326-2-2 Note: SONEL S.A. hereby declares that the radio device type MIC-30 complies with Directive 2014/53/EU. The full text of the EU Declaration of Conformity is available at the following website address: https://sonel.pl/en/download/declaration-...
SONEL S.A. Wokulskiego 11 58-100 Świdnica Poland tel. +48 74 858 38 60 fax +48 74 858 38 09 E-mail: export@sonel.pl Web page: www.sonel.pl NOTE Service repairs must be performed solely by the manufacturer. MIC-10 / MIC-30 – USER MANUAL...
Page 39
MEASURING MESSAGES CAUTION! Connecting the input terminals to voltages above 600V may cause damage to the meter and the risk of electrical injury to the user. Test voltage is present on terminals of the meter. You must consult the manual. The meter is ready for measurement.