Emerson Liebert CRV User Manual page 17

10-50 kw a/w/c, 50 hz
Hide thumbs Also See for Liebert CRV:
Table of Contents

Advertisement

2. Number of racks / length of the row
Standard application with one Liebert CRV unit is with 2-6 racks. The exact number of
racks depends on size of Liebert CRV unit used and heat load per rack. Whenever
applying more than 6 racks for one CRV or Heat load more than 10kW per rack contact
Liebert sales representative
2-6 racks (0.6-5 m)
C
R
V
3. Placement in the room
3.a. Width of Hot / Cold aisle
C
C
R
R
V
V
Good approach:
C
C
R
R
V
V
Not advised approach:
C
C
R
R
V
V
Note:
* Please refer also to Service area dimensions Fig. 1. - Enclosure C
For good air distribution it is recommended to
keep width of the cold aisle as small as possible
for single row server room. Otherwise the cold
air discharged by Liebert CRV unit is being led
far from server suction and hot air may by-
passed from hot aisle.
Exceptions where wider cold aisle may be used
are: applications with CoolFlex (Cold Aisle
Containment) or with two rows facing each
other.
For width of the hot aisle there are no prefer­
ences, there is just minimum requirement
needed for enough for service area*.
9