Relay Output E & F-Frame - Danfoss VLT HVAC Drive FC 102 Design Manual

110-1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

How to Install
relay1
5
5
relay2
Illustration 5.97 D-Frame Additional Relay Outputs
5.4.7 Relay Output E & F-Frame
Relay 1
Terminal 01: common
Terminal 02: normally open 240 V AC
Terminal 03: normally closed 240 V AC
Relay 2
Terminal 04: common
Terminal 05: normally open 400 V AC
Terminal 06: normally closed 240 V AC
Relay 1 and relay 2 are programmed in 5-40 Function Relay,
5-41 On Delay, Relay, and 5-42 Off Delay, Relay.
Use option module MCB 105 for additional relay outputs.
150
Design Guide
03
240Vac, 2A
02
400Vac, 2A
01
06
240Vac, 2A
05
400Vac, 2A
04
Danfoss A/S © Rev. 05/2014 All rights reserved.
relay1
03
02
01
relay2
06
05
04
Illustration 5.98 E- and F-Frame Additional Relay Outputs
5.4.8 Parallel Connection of Motors
The frequency converter can control several parallel-
connected motors. The total current consumption of the
motors must not exceed the rated output current I
the frequency converter.
When motors are connected in parallel, 1-29 Automatic
Motor Adaptation (AMA) cannot be used.
Small motors have relatively high ohmic resistance in the
stator, which can cause problems at start and low RPM.
The electronic thermal relay (ETR) of the frequency
converter cannot be used as motor protection for the
individual motor of systems with parallel-connected
motors. Provide further motor protection by e.g.
thermistors in each motor or individual thermal relays.
(Circuit breakers are not suitable as protection).
240Vac, 2A
240Vac, 2A
400Vac, 2A
for
INV
MG16C202