Installation and Set-up
Design Guide
Bit 05, Not used
Bit 05 is not used in the status word.
Bit 06, No error/triplock
Bit 06='0': The frequency converter is not in fault mode. Bit
06 = "1": The frequency converter is tripped and locked.
Bit 07, No warning/warning
Bit 07='0': There are no warnings. Bit 07 = '1': A warning
has occurred.
Bit 08, Speed ≠ reference/speed = reference
Bit 08='0': The motor is running but the present speed is
different from the preset speed reference. This can occur
when the speed ramps up/down during start/stop. Bit 08
= '1': The motor speed matches the preset speed
reference.
Bit 09, Local operation/bus control
Bit 09='0': [STOP/RESET] is activated on the control unit or
7
7
Local control in 3-13 Reference Site is selected. It is
impossible to control the frequency converter via serial
communication. Bit 09 = '1' It is possible to control the
frequency converter via the fieldbus/serial communication.
Bit 10, Out of frequency limit
Bit 10='0': The output frequency has reached the value in
4-11 Motor Speed Low Limit [RPM] or 4-13 Motor Speed High
Limit [RPM]. Bit 10 = "1": The output frequency is within
the defined limits.
Bit 11, No operation/in operation
Bit 11= '0': The motor is not running. Bit 11='1': The
frequency converter has a start signal or the output
frequency is greater than 0 Hz.
Bit 12, Drive OK/stopped, autostart
Bit 12='0': There is no temporary over temperature on the
inverter. Bit 12='1': The inverter stops because of overtem-
perature but the unit does not trip and resumes operation
once the overtemperature stops.
Bit 13, Voltage OK/limit exceeded
Bit 13 = '0': There are no voltage warnings. Bit 13 = '1': The
DC voltage in the intermediate circuit is too low or too
high.
Bit 14, Torque OK/limit exceeded
Bit 14 = '0': The motor current is lower than the torque
limit selected in 4-18 Current Limit. Bit 14 = '1': The torque
limit in 4-18 Current Limit is exceeded.
Bit 15, Timer OK/limit exceeded
Bit 15 = '0': The timers for motor thermal protection and
thermal protection do not exceed 100%. Bit 15 = '1': One
of the timers exceeds 100%.
All bits in the STW are set to '0' if the connection between
the Interbus option and the frequency converter is lost, or
an internal communication problem has occurred.