Danfoss VLT HVAC Drive FC 102 Design Manual page 182

110-1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Installation and Set-up
Coil
0
01
Preset reference LSB
02
Preset reference MSB
03
DC brake
04
Coast stop
05
Quick stop
06
Freeze freq.
07
Ramp stop
08
No reset
09
No jog
10
Ramp 1
11
Data not valid
12
Relay 1 off
13
Relay 2 off
14
Set up LSB
15
Set up MSB
16
No reversing
7
7
Frequency converter control word (FC profile)
Table 7.15 Coil Descriptions
Register Number
00001-00006
00007
00008
00009
00010-00990
01000-01990
02000-02990
03000-03990
04000-04990
...
49000-49990
50000
50010
...
50200
50210
Table 7.17 Holding Registers
* Used to specify the index number to be used when accessing an indexed parameter.
180
Design Guide
1
No DC brake
No coast stop
No quick stop
No freeze freq.
Start
Reset
Jog
Ramp 2
Data valid
Relay 1 on
Relay 2 on
Reversing
Description
Reserved
Last error code from an FC data object interface
Reserved
Parameter index*
000 parameter group (parameters 001 through 099)
100 parameter group (parameters 100 through 199)
200 parameter group (parameters 200 through 299)
300 parameter group (parameters 300 through 399)
400 parameter group (parameters 400 through 499)
...
4900 parameter group (parameters 4900 through 4999)
Input data: frequency converter control word register (CTW).
Input data: Bus reference register (REF).
...
Output data: frequency converter status word register (STW).
Output data: frequency converter main actual value register (MAV).
Danfoss A/S © Rev. 05/2014 All rights reserved.
Coil
0
33
Control not ready
34
Frequency converter not
ready
35
Coasting stop
36
No alarm
37
Not used
38
Not used
39
Not used
40
No warning
41
Not at reference
42
Hand mode
43
Out of freq. range
44
Stopped
45
Not used
46
No voltage warning
47
Not in current limit
48
No thermal warning
Frequency converter status word (FC profile)
Table 7.16 Coil Descriptions
1
Control ready
Frequency converter ready
Safety closed
Alarm
Not used
Not used
Not used
Warning
At reference
Auto mode
In frequency range
Running
Not used
Voltage warning
Current limit
Thermal warning
MG16C202

Advertisement

Table of Contents
loading