Danfoss VLT HVAC Drive FC 102 Design Manual page 143

110-1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

How to Install
91 (L1)
3 Phase
92 (L2)
power
93 (L3)
input
95
PE
DC bus
88 (-)
89 (+)
50 (+10 V OUT)
+10Vdc
53 (A IN)
0-10Vdc
0/4-20 mA
54 (A IN)
0-10Vdc
0/4-20 mA
55 (COM A IN)
12 (+24V OUT)
13 (+24V OUT)
18 (D IN)
19 (D IN)
20 (COM D IN)
27
(D IN/OUT)
29
(D IN/OUT)
32 (D IN)
33 (D IN)
*
37 (D IN)
Illustration 5.89 Interconnect Diagram E-frames and F-frames (6-pulse)
*Safe Torque Off (STO) input available with STO function
only
Very long control cables and analogue signals occasionally
result in 50/60 Hz ground loops due to noise from mains
supply cables.
In this case, break the screen or insert a 100 nF capacitor
between screen and chassis.
The digital and analogue inputs and outputs must be
connected separately to the common inputs (terminal 20,
55, 39) to avoid ground currents from both groups to
affect other groups. For example, switching on the digital
input disturbs the analogue input signal.
MG16C202
Design Guide
Switch Mode
Power Supply
24Vdc
15mA
200mA
+
-
+
S201
ON=0-20mA
S202
OFF=0-10V
P 5-00
24V (NPN)
0V (PNP)
24V (NPN)
0V (PNP)
24V (NPN)
0V (PNP)
24V
0V
24V (NPN)
0V (PNP)
24V
0V
24V (NPN)
0V (PNP)
24V (NPN)
0V (PNP)
Danfoss A/S © Rev. 05/2014 All rights reserved.
(U) 96
(V) 97
(W) 98
(PE) 99
(R+) 82
-
(R-) 81
relay1
03
02
01
relay2
06
05
04
(COM A OUT) 39
(A OUT) 42
S801
ON=Terminated
OFF=Open
5V
0V
S801
RS-485
(P RS-485) 68
Interface
(N RS-485) 69
(COM RS-485) 61
NOTICE
Control cables must be screened.
Motor
Brake
resistor
240Vac, 2A
240Vac, 2A
400Vac, 2A
Analog Output
0/4-20 mA
RS-485
(PNP) = Source
(NPN) = Sink
141
5
5