Copy sensor data
Service - PIN
VEGAPULS 63 • 4 ... 20 mA/HART - four-wire
6 Set up with the display and adjustment module PLICSCOM
In Multidrop mode, up to 15 sensors can be operated on one two-wire
cable. An address between 1 and 15 must be assigned to each sen-
sor.
7)
In this menu item you determine the HART mode and enter the ad-
dress for multidrop.
HART mode
Standard
Address 0
The default setting is standard with address 0.
This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the display
and adjustment module. A description of the function is available in
the operating instructions manual "Display and adjustment module".
The following data are read out or written with this function:
•
Measured value presentation
•
Adjustment
•
Medium
•
Inner diameter of the standpipe (with standpipe versions)
•
Vessel form
•
Damping
•
Linearisation curve
•
Sensor-TAG
•
Displayed value
•
Display unit
•
Scaling
•
Current output
•
Unit of measurement
•
Language
The following safety-relevant data are not read out or written:
•
HART mode
•
PIN
•
SIL
Copy sensor data
Copy sensor data?
In this menu item, the PIN is activated/deactivated permanently.
Entering a 4-digit PIN protects the sensor data against unauthorized
access and unintentional modifications. If the PIN is activated perma-
nently, it can be deactivated temporarily (i.e. for approx. 60 min.) in
any menu item. The instrument is delivered with the PIN set to 0000.
The 4 ... 20 mA signal of the sensor is switched off. The sensor uses a
7)
constant current of 4 mA. The measuring signal is transmitted exclusively as
a digital HART signal.