Vega VEGAPULS 63 Operating Instructions Manual page 15

4 ... 20 ma/hart - four-wire
Hide thumbs Also See for VEGAPULS 63:
Table of Contents

Advertisement

Inflowing medium
Mounting socket
VEGAPULS 63 • 4 ... 20 mA/HART - four-wire
Fig. 6: Vessel with conical bottom
Do not mount the instruments in or above the filling stream. Make sure
that you detect the product surface, not the inflowing product.
Fig. 7: Inflowing liquid
Flush mounting
The best way to mount the sensor, also with respect to cleanability,
is flush on a block flange (flange without socket piece) or through a
hygienic fitting.
Mounting on socket
If the reflective properties of the medium are good, you can mount
VEGAPULS 63 on a socket piece. You will find recommended values
for socket heights in the following illustration. The socket end should
be smooth and burr-free, if possible also rounded. Then carry out a
false signal suppression.
4 Mounting