Vega VEGAPULS 63 Operating Instructions Manual page 35

4 ... 20 ma/hart - four-wire
Hide thumbs Also See for VEGAPULS 63:
Table of Contents

Advertisement

Service - Reset
VEGAPULS 63 • 4 ... 20 mA/HART - four-wire
6 Set up with the display and adjustment module PLICSCOM
4. Push [OK]
The simulation is now running, with 4 ... 20 mA/HART a current is
outputted and with Profibus PA or Foundation Fieldbus a digital value.
How to interrupt the simulation:
Push [ESC]
Information:
The simulation is automatically terminated 10 minutes after the last
pressing of a key.
Simulation
Start simulation?
Basic adjustment
If the "Reset" is carried out, the sensor resets the values of the follow-
ing menu items to the reset values (see table):
Menu item
Max. adjustment
Min. adjustment
Medium
Vessel form
Damping
Linearization
Sensor-TAG
Displayed value
Extended settings
Current output - characteristics
Current output - max. current
Current output - min. current
Current output - failure
Unit of measurement
The values of the following menu items are not reset to the reset
values (see table) with "Reset":
Menu item
Backlight
Language
SIL
HART mode
Sensor-specific basic adjustment.
4)
Depending on the sensor type, see chapter "Technical data".
5)
4)
Reset value
0 m(d)
Meas. range end in m(d)
Liquid
not known
0 s
Linear
Sensor
Distance
None
4 ... 20 mA
20 mA
4 mA
< 3.6 mA
m(d)
Reset value
No reset
No reset
No reset
No reset
5)
35