WIRING
3.3 Connection cable
In the CC-Link system, use CC-Link dedicated cables.
If the cable used is other than the CC-Link dedicated cable, the performance of the CC-Link system is not
guaranteed.
For the specifications of the CC-Link dedicated cable, refer to the website of the CC-Link Partner
Association.
⋅ Website of the CC-Link Partner Association http://www.cc-link.org/
3.4 Wiring
(1) Strip off the sheath of the CC-Link dedicated cable and twist wires to use. If the length of the sheath
pealed is too long, a short circuit may occur among neighboring wires. If the length is too short, wires
might come off.
Use recommended cables. (Refer to page 16.) Recommended tightening torque : 0.22N⋅m to 0.25N⋅m
Wire the stripped cable after twisting it to prevent it from becoming loose. (Do not solder it.)
Cable stripping length
6.5mm
Use a blade type terminal as required.
16