[Explanation of table]
External
:Control by signal from external terminal is only valid.
NET
:Control from network is only valid
Combined
:Operation from either external terminal or communication is valid.
:Operation from either external terminal or computer is invalid.
Compensation
:Control by signal from external terminal is only valid if Pr. 28 Multi-speed input compensation setting is "1".
REMARKS
The Pr. 338 and Pr. 339 settings can be changed while the inverter is running when Pr. 77 = 2. Note that the setting
change is reflected after the inverter has stopped. Until the inverter has stopped, communication operation command
source and communication speed command source before the setting change are valid.
INVERTER SETTING
4
29