DETAILS OF INPUT AND OUTPUT SIGNALS

The following device No. are those for station 1.
For stations 2 and later, the device No. are different. (Refer to the master module manual for
correspondence between the device No. and station number)

7.1 Details of remote input and output signals

7.1.1

Output signals (master module to inverter (FR-A7NC))

The output signals from the master module are indicated. (Input signals to inverter)
Device
No.
RY0
Forward rotation command
RY1
Reverse rotation command
RY2
High-speed operation command (terminal RH function)
RY3
Middle-speed operation command (terminal RM function)
RY4
Low-speed operation command (terminal RL function)
RY5
Jog operation command (terminal Jog function)
RY6
Second function selection (terminal RT function)
RY7
Current input selection (terminal AU function)
Selection of automatic restart after instantaneous
RY8
power failure (terminal CS function)
RY9
Output stop
*2
RYA
Start self-holding selection (terminal STOP function)
RYB
Reset (RES terminal function)
*1
Signal names are initial values. Using Pr. 180 to Pr. 186, Pr. 188, and Pr .189, you can change input signal functions.
Note that some of signals do not accept a command from the network according to the Pr. 338 and Pr. 339 settings.
(Refer to page 26.)
*2
Signals of the RY0, RY1, and RY9 can not be changed. Even when changed using Pr. 178, Pr. 179, and Pr. 187,
the settings are invalid.
Refer to the inverter manual for details of Pr. 178 to Pr.189.
56
Signal
*2
*2
*1
*1
*1
*1
*1
*1
Description
0 : Stop command
1 : Forward rotation start
0 : Stop command
1 : Reverse rotation start
*1
*1
*1
Functions assigned to terminals RH, RM, RL, JOG, RT, AU,
and CS are activated.
Turn on the MRS signal to stop the inverter output.
Functions assigned to terminal STOP and RES are
activated.
When "1" is set, a start command
is input to the inverter.
When "1" is set in RY0 and RY1,
a stop command is input.