INVERTER SETTING
4.3.1

Communication EEPROM write selection (Pr. 342)

When parameter write is performed from the communication option, write to RAM is enabled. Set when
frequent parameter changes are necessary.
Parameter
Number
Communication EEPROM write
342
selection
⋅ When changing the parameter values frequently, set "1" in Pr. 342 to write them to the RAM.
Performing frequent parameter write with "0 (initial value)" (EEPROM write) set will shorten the life of the
EEPROM.
REMARKS
When "1" (write to RAM only) is set in Pr. 342, powering off the inverter will erase the changed parameter values.
Therefore, the parameter values available when power is switched on again are the values stored in EEPROM
previously.
30
Initial
Name
Value
Setting
Range
Parameter values written by
0
communication are written to the
EEPROM and RAM.
0
Parameter values written by
1
communication are written to the RAM.
Description