Technical Data; Device Data; Connection Type; Climatic Environmental Conditions - WAGO 750-616 Manual

I/o system 750 separation module without power jumper contacts
Table of Contents

Advertisement

16
Device Description
Pos : 19.21 /Alle Serien (Allgemeine M odul e)/Übersc hriften für all e Seri en/Gerätebes chr eibung/T ec hnis che D aten - Ü bersc hrift 2 @ 3\mod_1232967587687_21.doc x @ 26924 @ 2 @ 1
3.5

Technical Data

Pos : 19.22 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Tec hnische D aten/Systemklemmen/T echnisc he Daten 750- 0616 @ 20\mod_1408368833060_21.doc x @ 161958 @ 3 @ 1
3.5.1

Device data

Table 5: Technical data – device
Width
Height (from upper edge of 35 DIN rail) 64 mm
Depth
Weight
Pos : 19.23 /Alle Serien (Allgemeine M odul e)/Übersc hriften für all e Seri en/Gerätebes chr eibung/Anschl uss tec hni k - Ü bersc hrift 3 @ 17\mod_1380123271324_21.doc x @ 132788 @ 3 @ 1
3.5.2

Connection Type

Pos : 19.24 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Tec hnische D aten/Ans chl usstec hni k/Technisc he Daten Klemmenbus @ 17\mod_1380123495844_21.doc x @ 132794 @ @ 1
Table 6: Technical Data – Internal Bus
Data contacts
Pos : 19.25 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Tec hnische D aten/Klimatisc he U mweltbedingungen/T ec hnis che D aten Kli matisc he U mweltbedi ngungen o. er w. T empbereic h; 0...55°C/-25...+ 85° C @ 5\mod_1247657968368_21.doc x @ 37603 @ 3 @ 1
3.5.3

Climatic Environmental Conditions

Table 7: Technical Data – Climatic Environmental Conditions
Operating temperature range
Storage temperature range
Relative humidity without condensation Max. 95 %
Resistance to harmful substances
Maximum pollutant concentration at
relative humidity < 75 %
Special conditions
Pos : 19.26 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
WAGO-I/O-SYSTEM 750
750-616 Separation module
12 mm
100 mm
38.9 g
slide contact, hard gold plated, self-
cleaning
0 °C ... 55 °C
-25 °C ... +85 °C
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
≤ 25 ppm
SO
2
S ≤ 10 ppm
H
2
Ensure that additional measures for
components are taken, which are used in
an environment involving:
– dust, caustic vapors or gases
– ionizing radiation
Manual
Version 1.1.0