Mounting & Wiring Alarms - Ei Electronics Ei2110e Series Instruction Manual

Multi-sensor fire alarm with rechargeable lithium cell back-up
Table of Contents

Advertisement

1. Select a location complying with the
advice in previous sections (see pages
8-18).
2. Disconnect the AC mains supply from
the circuit that is going to be used.
3. Lift off the wiring cover as shown in
Figure 3.
The wiring must be connected to the terminal
block on the mounting plate as follows:
L: Live - connect to the house wires
coloured brown or marked L.
N: Neutral - connect to the house wires coloured blue or marked N.
IC: Interconnect - see Section 4.2 & Figure 6 for information on interconnection.
Note: Wiring must be installed in compliance with local regulations.
Warning: Mixing the Live and Neutral connections when interconnecting Alarms
will damage all the Alarms - ensure that the same colours are used throughout the
premises for Live, Neutral and Interconnect wires.
We strongly recommend that you check for the following before connecting the
Alarm:
• check for Live and Neutral using a two probe tester.
4.1 Mounting & Wiring Alarms
FOAM CEILING GASKET
Figure 3
15
INSERT SCREWDRIVER
TO LIFT AND REMOVE
WIRING COVER