Mounting & Wiring Alarms - Ei Electronics Ei160e Series Instruction Manual

230v~ smoke & heat alarms
Hide thumbs Also See for Ei160e Series:
Table of Contents

Advertisement

WARNING: Mains operated Alarms should be installed
and interconnected by a qualified electrician in accordance
with the Regulations for Electrical Installations published
by the Institution of Electrical Engineers (BS7671).
Failure to install this Alarm correctly may expose the
user to shock or fire hazards.
WARNING: The Alarm must be continuously powered
24 hours a day so it is important that it is not on a circuit
that can be turned off by a switch.
Note: BS 5839-6: 2013 gives the folowing recommendations
regarding the mains supply to be used in a Grade D system (The
Ei161e, Ei166e Smoke Alarms and Ei164e Heat Alarms can be
used in a Grade D system). The power supply for the Alarms
should be derived from the public electricity supply to the dwelling.
The mains supply to the Alarms should take the form of either:
(a) an independent circuit at the dwelling's main distribution
board, in which case no other electrical equipment should be
connected to this circuit (other than a dedicated monitoring
device installed to indicate failure of the mains supply to the
Alarms); or
(b) a separately electrically protected, regularly used local lighting
circuit.
Alarms should be connected on a single final circuit, unless the
means of interconnection is by radio signals (e.g. RadioLINK).
(See BS 5839-6: 2013 for further information)
Note: The Ei100MRF RadioLINK
eliminate interconnect wiring, make system extensions and
provide simple and cost effective compliance with BS 5839-6:
2013.
Mounting & Wiring Alarms
1. Select a location complying with the advice in the
(Positioning Alarms section).
2. Disconnect the AC mains supply from the circuit that
is going to be used.
3. Lift off the wiring cover as shown in Figure 3.
The house wiring must be connected to the terminal block
on the mounting plate as follows:
L: Live - connect to the house wires coloured brown or
marked L.
N: Neutral - connect to the house wires coloured blue
or marked N.
FOAM CEILING GASKET
Figure 3
See page 16 for information on interconnection.
Note: Wiring must be installed in compliance with local
regulations.
Warning: Mixing the Live and Neutral connections
when interconnecting alarms will damage all the
alarms - ensure that the same colours are used
throughout the premises for Live, Neutral and
Interconnect wires.
We strongly recommend that you check for the following
before connecting the Alarm:
Module can be used to
+
INSERT SCREWDRIVER
TO LIFT AND REMOVE
WIRING COVER
14

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ei161eEi164eEi166e

Table of Contents