Precautions Regarding the Hardware

Comparison of FX3U and FX5U and Precautions for Replacement
The following list shows precautions of the hardware. Check details in the manuals of each model when replacing.
■Difference and precautions regarding the main hardware of FX3U and FX5U
Item
Extension of FX2N and FX3U
Input hardware filter
(When the digital filter is 0)
• High-speed counter
• Input interruption function
• Pulse catch function
Input signal current
■External dimension drawing
There is some difference in the external dimension of FX3U and the successor model FX5U. Be careful when replacing the
modules.
• FX3U
2-4.5-diam mounting hole (16M, 32M)
4-4.5-diam mounting hole (48M to 128M)
There is no mounting hole * for 16M and 32M.
*
22
W1 (mounting hole pitch)
W
Model name
FX3U-16M
FX3U-32M
FX3U-48M, FX3U-32MR/UA1
FX3U-64M
FX3U-80M, FX3U-64MR/UA1
FX3U-128M
Difference
FX3U
FX5U
Extension possible
Extension is possible only for
certain modules.
FX5-CNV-BUS is required for
extension.
X0 to X5 are 5μs.
There is no 0 setting.
X6 to X7 are 50μs.
X10 to X17 are 200μs.
X0 to X5 are 6 mA.
X0 to X17 are 5.3 mA.
X6 to X7 are 7 mA.
X20 and subsequent are 4 mA.
X10 and subsequent are 5 mA.
*
W: mm
130
150
182
220
285
350
Precautions
Connection is not possible for some intelligent
modules of FX3U.
There is no 0 setting, but no setting can be
selected (no filter).
Noises that were not detected by FX3U may
possibly be captured as an input. If necessary,
take measures against external noises.
The input signal current has been lowered, so it
is necessary to check the specification of the
external devices when replacing.
9
86 (When FX3U-7DM installed: 88.5)
W1: mm
103
123
155
193
258
323
2 Replacement from FX3U to FX5U
2.3 Selection of Substitute Models
External color: Munsell 0.08GY/7.64/
0.81
Top cover: Munsell N1.5
Unit: mm
The terminal block uses M3 terminal
screws
35 mm width DIN rail can be
installed
Weight: kg
0.60
0.65
0.85
1.00
1.20
1.80
2
23

Advertisement