1--2 Wiring - Omron SYSMAC C2000H Operation Manual

Analog i/o units
Hide thumbs Also See for SYSMAC C2000H:
Table of Contents

Advertisement

3--1--2
Wiring
Voltage Inputs
VOLTAGE ONLY

AD001
+1

AD002
0
+10VDC

AD003
0
+5VDC

AD004
--10

AD005
--5
Use shielded twisted-pair cable for external connections.
Connect the positive and negative terminals of any unused input points to the
shield terminal.
Use separate power supplies for input points 1 and 2 whenever possible.
When using separate power supplies, always connect the negative input ter-
minal to the shield line; failure to do so will produce several percent of error
in the converted data.
Incorrect wiring will produce inaccuracy in converted data. Use the proper
wiring diagram and wire with care.
+5VDC
+10VDC
+5VDC
+
--
+
--
0
1
2
3
4
NC
5
6
7
8
NC
9
10
NC
11
NC
12
NC
13
NC
14
NC
15
NC
16
NC