Quick Start Guide
IG IECEx FISCO
Certificate: IECExBAS08.0045X
Standards: IEC60079-0:2011, IEC60079-11:2011
Markings: Ex ia IIC T4 Ga (–60 °C ≤ T
Table 7. Input Parameters
Parameter
Voltage U
Current I
i
Power P
i
Capacitance C
Inductance L
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90 V transient suppressor, it is incapable of
withstanding the 500 V isolation from earth test and this must be taken into account
during installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane
paint finish; however care should be taken to protect it from impact and abrasion when
located in Zone 0.
N7 IECEx Type n
Certificate: IECExBAS08.0046X
Standards: IEC60079-0:2011, IEC60079-15:2010
Markings: Ex nA IIC T4 Gc (–40 °C ≤ T
Special Condition for Safe Use (X):
1. If fitted with a 90 V transient suppressor, the equipment is not capable of withstanding
the 500 V electrical strength test as defined in clause 6.5.1 of IEC60079-15:2010. This
must be taken into account during installation.
9.6 Brazil
E2 INMETRO Flameproof
Certificate: UL-BR 14.0375X
Standards: ABNT NBR IEC60079-0:2008 + Errata 1:2011,
Markings: Ex d IIC T6/T5 Gb IP66, T6(–50 °C ≤ T
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm. Installation, maintenance and use shall take
into account the environmental conditions to which the diaphragm will be subjected.
The manufacturer's instructions for installation and maintenance shall be followed in
detail to assure safety during its expected lifetime.
2. The Ex d blanking elements, cable glands, and wiring shall be suitable for a temperature
of 90 °C.
3. In case of repair, contact the manufacturer for information on the dimensions of the
flameproof joints.
24
FISCO
17.5 V
i
380 mA
5.32 W
0 nF
i
0 μH
i
ABNT NBR IEC 60079-1:2009 + Errata 1:2011,
ABNT NBR IEC 60079-26:2008 + Errata 1:2009
≤ +60 °C)
a
≤ +70 °C)
a
≤ +65 °C), (–50 °C ≤ T
a
September 2016
≤ +80 °C)
a

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount 2051cf series

Table of Contents