Danfoss AK-SM 350 Manual page 30

Monitoring unit with alarm function and data collection
Table of Contents

Advertisement

The following settings only apply if "Controller" was selected in point
3.
Controller
This list of settings was
previously covered under
temperature. Please see the
explanation on pages 24-25.
Select a predefined set of readouts
There are several sets to choose from. Select the set that repre-
sents the temperature controller in question:
1
When it is a temperature controller or a refrigeration ap-
plication control for one section.
2
When it is a refrigeration application control for two sec-
tions and a readout for Section 2 is required.
Or it is a compressor or condenser control and a readout of
the condenser control is required.
3
When it is a refrigeration application control for three sec-
tions
4
When it is a refrigeration application control for four sec-
tions.
Select 1-99 for wireless. This number will display the node with
the same number.
30
Manual RS8EF402 © Danfoss 02-2009
Alarm limits
The alarm limits must be set for the different controllers.
It is the individual controllers that emit alarms.
The alarms are received by the AK-SM 350, which then presents
them.
If an alarm limit has to be changed in a controller, this can be
done from the AK-SM 350 via the "More details" screen.
Controller address.
(1 or 11 is the network
number and cannot be
changed.)
AK-SM 350 Version 1.7x