Warnings and Alarms
VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
77 WARNING, Reduced power mode
This warning indicates that the frequency converter is
operating in reduced power mode (i.e. less than the
allowed number of inverter sections). This warning will be
generated on power cycle when the frequency converter is
set to run with fewer inverters and will remain on.
ALARM 79, Illegal power section configuration
The scaling card is the incorrect part number or not
installed. Also MK102 connector on the power card could
not be installed.
ALARM 80, Drive initialised to default value
Parameter settings are initialised to default settings after a
manual reset. Reset the unit to clear the alarm.
ALARM 81, CSIV corrupt
CSIV file has syntax errors.
ALARM 82, CSIV parameter error
CSIV failed to init a parameter.
ALARM 85, Dang fail PB:
Profibus/Profisafe Error.
WARNING/ALARM 104, Mixing fan fault
The fan monitor checks that the fan is spinning at drive
power-up or whenever the mixing fan is turned on. If the
fan is not operating, then the fault is annunciated. The
mixing-fan fault can be configured as a warning or an
alarm trip by parameter 14-53 (Fan Monitor).
Troubleshooting Cycle power to the frequency converter
to determine if the warning/alarm returns.
WARNING 250, New spare part
A component in the frequency converter has been
replaced. Reset the frequency converter for normal
operation.
WARNING 251, New typecode
The power card or other components have been replaced
and the typecode changed. Reset to remove the warning
and resume normal operation.
MG21E122 - VLT® is a registered Danfoss trademark
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
8
8
8-11

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT FC 322 and is the answer not in the manual?

Questions and answers

Table of Contents