Setpoint Ramp/Soak Programming and Operation - Setpoint Program Profiles Set Up Group

6.6 Setpoint Program Profiles Set Up Group

Introduction
You can configure up to six profiles; each profile contains a subset of the 36 segments. Each profile starts
with a ramp segment and ends with a soak segment. Each control loop uses one of these profiles. They can
use the same profile, too. The profiles can be synchronized to RUN/HOLD together.
Setpoint program profiles group prompts
Table 6-4 lists all the function prompts in the Setpoint Program Profiles setup group and their definitions.
Lower Display
Prompt
Range of Setting or Selection
RAMP1 – RAMP 35
PRx STRT
SOAK2 – SOAK36
PRx END
RAMPUNIT
TIME (Hours:Minutes)
EU/MIN (Engineering
Units/Minute)
EU/HR (Engineering Units/Hour)
SYNC 1+2
ENABLE
DISABL
Release M
DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual
April 2017

Table 6-4 Setpoint program profiles group definitions

Upper Display
Parameter Definition
You can configure up to 6 profiles (PR1 – PR6). Each
profile contains a subset of the 36 ramp and soak
segments configured later. PRx STRT designates the
number of the first segment of the profile. It must be a
ramp segment (odd number).
This designates the number of the last segment of the
profile. It will be a soak segment (even number).
This determines the engineering units for the ramp
segments.
Synchronizes the profiles for Control Loops 1 and 2.
This means that:
a)
Both SP programs will RUN or HOLD
simultaneously.
b)
A Guaranteed Soak Hold on one profile will cause
the other profile to HOLD for the duration of the
Guaranteed Soak Hold.
163