Table 8-5 Auxiliary Output Calibration Procedure - Honeywell DR4500A Product Manual

Classic series circular chart recorder with or without control
Hide thumbs Also See for DR4500A:
Table of Contents

Advertisement

The procedure for calibrating the Auxiliary Output is listed in Table 8-5. Make sure "LOCKOUT" in the
Set Up group is set to "NONE." See Section 3 – Configuration. Also, "AUX OUT" must NOT be disabled.
Step
Operation
1
Enter Calibration Mode
2
Calibrate 0 %
3
Calibrate 100 %
4
Exit the Calibration Mode
ATTENTION
The calibration for Auxiliary Outputs #2 and #3 follows the procedure for calibrating the current
proportional output (refer to Subsection 8.2).
Release M
DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual
April 2017

Table 8-5 Auxiliary output calibration procedure

Press
SET
UP
FUNC
or
FUNC
or
FUNC
LOWR
DISP
or
SET
UP
Output Calibration - Auxiliary Output Calibration
Action/Result
Until you see:
Upper Display: CALIB
Lower Display: AUX OUT
You will see:
Upper Display: (a value)
(approximately 750)
Lower Display: ZERO VAL
Until the desired 0 % (4 mA) output is read on the
milliammeter.
Stores the 0 % value and you will see:
Upper Display: (a value)
(approximately 3650)
Lower Display: SPAN VAL
Until the desired 100 % (20 mA) output is read on the
milliammeter.
The recorder stores the span value.
To exit the calibration mode.
201