Output Calibration; Overview - Honeywell DR4500A Product Manual

Classic series circular chart recorder with or without control
Hide thumbs Also See for DR4500A:
Table of Contents

Advertisement

194

8.1 Overview

SHOCK HAZARD—WARNING!
Disregard of these instructions may cause injury or death.
OUTPUT CALIBRATION MAY REQUIRE ACCESS TO HAZARDOUS LIVE CIRCUITS, AND
SHOULD ONLY BE PERFORMED BY QUALIFIED SERVICE PERSONNEL. MORE THAN
ONE SWITCH MAY BE REQUIRED TO DE-ENERGIZE UNIT BEFORE CALIBRATION.
Introduction
This section describes the field calibration procedures for the following types of outputs:
Current Output
Position Proportional Output
Auxiliary Output
ATTENTION
Calibration for Control Outputs #1 and #2 is identical except for the particular printed circuit
board involved.
What's in this section
This section contains the following topics:
8.1
Overview
8.2
Current Proportional Output/Aux Out 2 and 3 Calibration
8.3
Position Proportional Output Calibration
8.4
Auxiliary Output Calibration
Release K
DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual
May 2013

8. Output Calibration

Topic
● Introduction
● Equipment needed
● Calibrator connections
● Calibration Procedure
● Position proportional control
● Equipment needed
● Connections
● Auto mode vs manual mode
● Displayed values
● Calibration Procedure
● Introduction
● Equipment needed
● Calibrator connections
● Calibration Procedure
See Page
194
195
195
195
195
196
197
197
197
197
197
197
197
200
200
200
200
200
194

Advertisement

Table of Contents
loading

Table of Contents