Honeywell DR4500A Product Manual page 101

Classic series circular chart recorder with or without control
Hide thumbs Also See for DR4500A:
Table of Contents

Advertisement

Lower Display
Prompt
Range of Setting or Selection
PENnON
0 to 100%
(n = 1 or 2)
PENnOFF
0 to 100%
(n = 1 or 2)
Repeat this procedure for PEN 2 configuration.
Release M
DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual
April 2017
Upper Display
Configuration Parameter Definitions
Parameter Definition
PEN CHART POSITION FOR ON EVENT — This is the
event marker configuration using digital inputs.
Select the chart position where pen 1 (pen 2) is to mark
(trace) occurrence of an ON event.
Prompt only appears if DGTL1 or 2 is selected as pen
1 (pen 2) input.
PEN CHART POSITION FOR OFF EVENT — This is
the event marker configuration using digital inputs.
Select the chart position where pen 1 (pen 2) is to mark
(trace) occurrence of an OFF event.
Prompt only appears if DGTL1 or 2 is selected as
pen 1 (pen 2) input.
Pen Parameters Set Up Group
87