Alarm Setpoints; Table 5-25 Procedure For Displaying Or Changing The Alarm Setpoints - Honeywell DR4500A Product Manual

Classic series circular chart recorder with or without control
Hide thumbs Also See for DR4500A:
Table of Contents

Advertisement

Operation - Alarm Setpoints

5.11 Alarm Setpoints

Introduction
An alarm consists of a relay contact and an operator interface indication. The alarm relay is de-energized
if Alarm Setpoint 1 or Setpoint 2 is exceeded.
The alarm relay is energized when the monitored value goes into the allowed region by more than the
hysteresis.
There are twelve alarm setpoints, two for each alarm.
The type and state (High or Low) is selected during configuration: see Section 3 - Configuration for
details.
ATTENTION
An active alarm will always provide an indication on the display but may not control the relay;
that is, a higher priority function such as a control loop or timer may have control of the relay.
Procedure for displaying the alarm setpoints
The procedure for displaying and changing the alarm setpoints is listed in

Table 5-25 Procedure for displaying or changing the alarm setpoints

Step
Operation
1
Access the Alarm Set Up
group
2
Access the Alarm
Setpoint Values
3
Return to normal
operation
142
DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual
Press
SET
Until you see:
UP
Upper Display: SET UP
Lower Display: ALARM X
FUNC
Successively displays the alarm setpoints and their
values.
Upper Display: The alarm setpoint value
Lower Display: AXS1 VAL – Setpoint 1 value of
Change any alarm setpoint value you select in the
or
upper display.
LOWR
Returns to normal operation.
DISP
T able 5-25.
8 3 H
Action/Result
X = 1, 2, 3, 4, 5, 6
alarm 1, 2, 3, 4, 5, or 6
AXS2 VAL – Setpoint 2 value of
alarm 1, 2, 3, 4, 5, or 6
Release M
April 2017

Advertisement

Table of Contents
loading

Table of Contents