Diagnostics
6.1 Diagnosis using LEDs
PRE_1, PRE_2
RxD_1, RxD_2
The meaning of the individual flash patterns and the associated fault/error descriptions can be
1)
found in the relevant FB and FC documentation.
2)
within the range of influence of the reader.
Table 6- 2
BF
On
flashes
flashes
On
Off
On
– = Status not relevant
44
LEDs
RFID: Indicates the presence of a transponder.
2)
MV: LED on - camera on and in stop mode
LED off - no connection to camera or error status on camera
LED flashes - a flashing pattern shows the value of "number_MDS".
Indicates live communication with the reader. May also indicate malfunctions on
the reader.
In multitag mode, this LED uses a flash interval to indicate the number of data carriers currently
LED display for PROFIBUS diagnosis
SF
–
ASM is in start-up mode.
•
Connection to DP Master failed.
•
ASM not detecting a baud rate
•
Bus interrupt
•
DP Master not functioning
•
On
The project data sent to the ASM
•
by the DP Master do not match the
configuration of the ASM.
–
ASM has detected the baud rate,
•
but is not activated by the DP Mas-
ter.
ASM has not been assigned project
•
plans.
flashes
There is a hardware defect in the
•
ASM.
On
Diagnosis available
•
Off
The set PROFIBUS address is
•
incorrect or greater than 99.
Meaning
Cause of error
Operating Instructions, 07/2015, J31069-D0162-U001-A6-7618
Error handling
–
Check the PROFIBUS DP connec-
•
tion.
Check the DP Master
•
Check all cables on your
•
PROFIBUS DP network.
Check whether the connector plugs
•
for the PROFIBUS DP are securely
plugged into the ASM.
Check the project for the ASM
•
(input/output, PROFIBUS address).
Correct GSD file being used?
•
Check the PROFIBUS address set
•
in ASM and/or in the project soft-
ware.
Check the project for the ASM
•
(station type).
Replace the ASM.
•
Evaluate the diagnostic information.
•
Set the address in the range 1 to 99
•
and carry out new run-up.
ASM 456 interface module