Operating Guide
MENU > Settings > Return limit
Priority (priority for return temp. limitation)
Circuit
All
Choose whether the return temperature limitation should overrule the set
min. flow temperature 'Temp. min.' .
* See Appendix "Parameter ID overview"
OFF:
The min. flow temperature limit is not overruled.
ON:
The min. flow temperature limit is overruled.
74
DEN-SMT/DK
ECL Comfort 310, application A368
1x085
Factory setting
Setting range
*
If you have a DHW application:
Please also see 'Parallel operation' (ID 11043).
*
If you have a DHW application:
When dependent parallel operation is in function:
•
Desired flow temperature for the heating circuit will be minimum
limited, when "Priority for return temperature" (ID 1x085) is set
to OFF.
•
Desired flow temperature for the heating circuit will not be
minimum limited, when "Priority for return temperature"
(ID 1x085) is set to ON.
VI.LG.J3.02
Danfoss District Energy