Operating Guide
MENU > Settings > Control par., fan
MENU > Settings > Flow / power limit
Limit (limitation value)
Circuit
All
This value is in some applications a calculated limitation value, based on the
actual outdoor temperature.
In other applications the value is a selectable limitation value.
* See Appendix "Parameter ID overview"
MENU > Settings > Flow / power limit
Adapt. time (adaptation time)
Circuit
All
Controls how fast the flow / power limitation adapts to the desired
limitation.
* See Appendix "Parameter ID overview"
OFF:
The control function is not influenced by the 'Adapt.
time' .
Minor
The desired temperature is adapted quickly.
value:
Major
The desired temperature is adapted slowly.
value:
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Flow / power limit
MENU > Settings > Refill tank
MENU > Settings > S7 (S8, S9, S10) pressure
Filter constant
Circuit
All
The value of the filter constant determines the dampening of the measured
value.
The higher the value, the more dampening.
By this, a too quick change of the measured value can be avoided.
* See Appendix "Parameter ID overview"
Minor
Lower dampening
value:
Major
Higher dampening
value:
Danfoss District Energy
ECL Comfort 310, application A368
1x111
Setting range
Factory setting
*
1x112
Factory setting
Setting range
*
1x113
Factory setting
Setting range
*
*
If the 'Adapt. time' is too low, there is a risk of unstable control.
*
*
VI.LG.J3.02
DEN-SMT/DK
77