Operating Guide
MENU > Settings > Application
Ext. mode (external override mode)
Circuit
COMFORT / SAVING /
FROST PR. / CONST. T
The mode override can be activated for Saving, Comfort, Frost pr. or
Constant T mode.
For override, the controller mode must be in scheduled mode.
Choose an override mode:
SAVING:
The circuit in question is in saving mode when the
override switch is closed.
COMFORT:
The circuit in question is in comfort mode when the
override switch is closed.
FROST PR.:
The heating or DHW circuit closes, but is still frost
protected.
CONSTANT T: The circuit in question controls a constant
temperature *)
*)
See also 'Desired T' (1x004), setting of desired flow
temperature (MENU > Settings > Flow temperature)
See also ' Con. T, ret. T lim.' (1x028), setting of return
temperature limitation (MENU > Settings > Return
limit)
The process diagrams show the functionality.
Danfoss District Energy
ECL Comfort 310, application A368
1x142
Setting range
Factory setting
COMFORT
See also 'Ext. input' .
Example: Override to Comfort mode
# 1 # = Override switch (not activated / activated)
# 2 # = Function mode (Schedule / Comfort)
# 3 # = Time
Example: Override to Saving mode
# 1 # = Override switch (not activated / activated)
# 2 # = Function mode (Schedule / Saving)
# 3 # = Time
The result of override to 'Saving' mode depends on the setting in
'Total stop'.
Total stop = OFF: Heating reduced
Total stop = ON: Heating stopped
VI.LG.J3.02