7.7 Parameter ID overview

A368.x — x refers to the subtypes listed in the column.
ID
Parameter Name
10609
Low Y
10610
High Y
10656
Alarm value
10657
Alarm time-out
10676
Alarm value
10677
Alarm time-out
11004
Desired T
11011
Auto saving
11012
Boost
11013
Ramp
11014
Optimizer
11017
Demand offset
11021
Total stop
11022
P exercise
11023
M exercise
11026
Pre-stop
11028
Con. T, ret. T lim.
11029
DHW, ret. T limit
11031
High T out X1
11032
Low limit Y1
11033
Low T out X2
11034
High limit Y2
11035
Infl. - max.
11036
Infl. - min.
11037
Adapt. time
11043
Parallel operation
11052
DHW priority
11077
P frost T
11078
P heat T
11085
Priority
11093
Frost pr. T
11109
Input type
11112
Adapt. time
11113
Filter constant
158
DEN-SMT/DK
ECL Comfort 310, application A368
A368.x
Setting range
3, 4, 5
0.0 ... 30.0
3, 4, 5
0.0 ... 30.0
1, 2, 3, 4, 5, 6
OFF ; ON
1, 2, 3, 4, 5, 6
0 ... 240
3, 4, 5
OFF ; ON
3, 4, 5
0 ... 240
1, 2, 3, 4, 5, 6
5 ... 150
1, 2, 3, 4, 5, 6
OFF, -29 ... 10
1, 2, 3, 4, 5, 6
OFF, 1 ... 99
1, 2, 3, 4, 5, 6
OFF, 1 ... 99
1, 2, 3, 4, 5, 6
OFF, 10 ... 59
1, 2, 3, 4, 5, 6
OFF, 1 ... 20
1, 2, 3, 4, 5, 6
OFF ; ON
1, 2, 3, 4, 5, 6
OFF, 1 ... 200
1, 2, 3, 4, 5, 6
OFF ; ON
1, 2, 3, 4, 5, 6
OFF ; ON
1, 2, 3, 4, 5, 6
10 ... 110
1, 2, 3, 4, 5, 6
OFF, 10 ... 110
1, 2, 3, 4, 5, 6
-60 ... 20
1, 2, 3, 4, 5, 6
10 ... 150
1, 2, 3, 4, 5, 6
-60 ... 20
1, 2, 3, 4, 5, 6
10 ... 150
1, 2, 3, 4, 5, 6
-9.9 ... 9.9
1, 2, 3, 4, 5, 6
-9.9 ... 9.9
1, 2, 3, 4, 5, 6
OFF, 1 ... 50
1, 2, 3, 4, 5, 6
OFF, 1 ... 99
1, 2, 3, 4, 5, 6
OFF ; ON
1, 2, 3, 4, 5, 6
OFF, -10 ... 20
1, 2, 3, 4, 5, 6
5 ... 40
1, 2, 3, 4, 5, 6
OFF ; ON
1, 2, 3, 4, 5, 6
5 ... 40
1, 2, 3, 4, 5, 6
EM1 ; EM2 ;
EM3 ; EM4 ;
EM5 ; OFF
1, 2, 3, 4, 5, 6
OFF, 1 ... 50
1, 2, 3, 4, 5, 6
1 ... 50
Factory
Unit
0.0
Bar
20.0
Bar
OFF
5
Sec
OFF
5
Sec
50
°C
-15
°C
OFF
%
OFF
Min
OFF
K
OFF
OFF
OFF
Sec
OFF
ON
70
°C
OFF
°C
15
°C
40
°C
-15
°C
60
°C
0.0
0.0
25
Sec
OFF
K
OFF
2
°C
20
°C
OFF
10
°C
OFF
OFF
Sec
10
VI.LG.J3.02
Own settings
Danfoss District Energy

Hide quick links: