Operating Guide

5.9 Application

The section "Application" describes specific application related
issues.
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Application
Demand offset
Circuit
All
The desired flow temperature in heating circuit 1 can be influenced by the
demand for a desired flow temperature from another controller (slave) or
another circuit.
* See Appendix "Parameter ID overview"
OFF:
The desired flow temperature in circuit 1 is not
influenced by the demand of any other controller (slave
or circuit 2).
Value: The desired flow temperature is increased by the set
value in 'Demand offset' , if the demand of the slave /
circuit 2 is higher.
Danfoss District Energy
ECL Comfort 310, application A368
1x017
Setting range
Factory setting
*
Heating application
*
=
X
Time
=
Y
Desired flow temperatures
=
# 1 #
Demand offset
=
# 2 #
Desired flow temperature, master
=
# 3 #
Desired flow temperature, slave
'Demand offset' with a value is to be used in the Master controller only.
The function of 'Demand offset' can compensate for heat losses
between master and slave controlled systems.
When setting "Demand offset" to a value, the return temperature
limitation will react according to the highest limitation value (Heating
/ DHW).
VI.LG.J3.02
DEN-SMT/DK