Operating Guide
MENU > Alarm > Charge T
MENU > Alarm > Temp. monitor
Lowest temp.
Circuit
All
The alarm function will not be activated if the desired flow / duct
temperature is lower than the set value.
* See Appendix "Parameter ID overview"
Clear alarm
If an alarm has been generated, a bell
the favorite display (see 'Monitoring temperatures and system
components') or in an overview display (see 'Understanding the
controller display'). The following menus are used to locate the
alarm cause and reset (clear) the alarm signal. Even when the cause
of the alarm has disappeared, the indication will still be active until
the clear alarm procedure has been carried out.
MENU > Alarm> Clear alarm
Circ. pumps
Circuit
All
Choose whether the alarm should be cleared or not.
* See Appendix "Parameter ID overview"
OFF:
The alarm has not been activated.
ON:
The alarm has been activated.
Clear alarm procedure:
If the status is 'ON': Change 'ON' to 'OFF' .
If the status is 'OFF': It is not possible to change it to 'ON' .
MENU > Alarm> Clear alarm
Refill water
Circuit
All
Choose whether the alarm should be cleared or not.
* See Appendix "Parameter ID overview"
OFF:
The alarm has not been activated.
ON:
The alarm has been activated.
Clear alarm procedure:
If the status is 'ON': Change 'ON' to 'OFF' .
If the status is 'OFF': It is not possible to change it to 'ON' .
116
DEN-SMT/DK
ECL Comfort 310, application A368
1x150
Setting range
Factory setting
*
is shown in one of
1x315
Factory setting
Setting range
*
1x324
Setting range
Factory setting
*
If the cause of the alarm disappears, the alarm indication and output
also disappear.
*
*
*
VI.LG.J3.02