Piping Diagram
7-3 Functions (cont.)
7-3-3 Others

7-3-3-1 Field Setting

Emergency operation for compressor malfunction
Purpose
Perform emergency operation until servicing if there is compressor failure when using more than one compressor.
Concept
Faulty compressors are disabled and turned off.
Control specifications in detail
Disabled compressors are excluded from capacity distribution, heat treatment of winding wire, protective control, and
self-diagnosed error detection.
Setting Outdoor
Seg1
Individual
0
Notes
- The performance may degrade if this option is changed.
- Make sure to return the option to the default value after servicing the compressor.
- Error E560 will be triggered if all the compressors on outdoor units are disabled.
(The SVC V/V must be closed for outdoor units if modules are installed and all the compressors on a single
outdoor unit are disabled.)
Samsung Electronics
Seg2
Seg3
0
0
0
0
Seg4
Emergency operation for compressor malfunction
0
1
Set compressor 1 as malfunction state
2
Set compressor 2 as malfunction state
Disabled (Default)
248