Samsung AM080FXWANR Service Manual page 75

System air conditioners outdoor unit
Hide thumbs Also See for AM080FXWANR:
Table of Contents

Advertisement

Troubleshooting
4-2 Service Operation (cont.)
4-2-1 Special Operation (cont.)
Forced oil recovery operation
Forced oil recovery operation : Oil recovery in the outdoor unit for the purpose of moving, installation if necessary.
Method of Entry
K2 Tact Switch 7 times
Start pattern
Water temperature is more than 10°C : Cooling Auto Trial Operation
Water temperature is less than or equal to 10°C : Heating Auto Trial Operation
Oil recovery start
Oil recovery start : It is after 10 minutes which Safety Start finishes.
Etc.
Oil recovery shut down and stop the normal pattern of the outdoor unit stop.
Samsung Electronics
72