Samsung AM080FXWANR Service Manual page 252

System air conditioners outdoor unit
Hide thumbs Also See for AM080FXWANR:
Table of Contents

Advertisement

Piping Diagram
7-3 Functions (cont.)
7-3-3 Others (cont.)
7-3-3-1 Field Setting (cont.)
Current restriction rate
Purpose
Reduce the electric current used for operation.
Concept
The max electric current (50% - 100%) is restricted.
Control specifications in detail
- The maximum current for outdoor units is restricted according to the current ratio that was configured while in cooling
or heating mode.
- See "Maximum current limit (total)" for details.
Input unit
Seg1
Individual
0
Notes
- When current restriction option is set, cooling and heating performance may decrease and power of
outdoor will increase.
- To set no restriction, make sure to contact an expert install service provider.
Outdoor units operate with an abnormal current.
This may affect the power and operation. The electric current protective control remains on to protect the units.
Oil collection interval
Purpose
The oil return cycle is shortened by half.
Concept
- Oil recovery is performed at the halved oil return interval.
- See "Oil return operation" for details on oil return operation specifications.
Input unit
Seg1
Main
0
Notes
Change the option if an oil leak occurs. Performance may degrade if the option is not changed.
Make sure to restore the original value after refilling the oil.
Samsung Electronics
Seg2
Seg3
0
0
0
0
0
0
2
0
0
0
0
1
1
Seg2
Seg3
0
4
0
Seg4
Current restriction rate
0
1
2
3
4
5
6
7
8
9
0
1
Seg4
Oil collection interval
0
1
Shorten the interval by 1/2
100% (default)
95%
90%
85%
80%
75%
70%
65%
60%
55%
50%
No restriction
Standard (default)
251

Advertisement

Table of Contents
loading

Table of Contents