Drain Pump Control - Samsung AM080FXWANR Service Manual

System air conditioners outdoor unit
Hide thumbs Also See for AM080FXWANR:
Table of Contents

Advertisement

Piping Diagram
7-3 Functions (cont.)
7-3-2 Control (cont.)
7-3-2-6 Indoor unit control (cont.)

Drain Pump Control

Purpose
Discharge the condensate stagnating in the indoor unit's drainage plate to prevent the condensate from overflowing
indoor units.
Concept
If the amount of condensate stagnating in the drainage plate reaches a certain level where it may overflow, the Float soft-
ware detects this and activates the drain pump to discharge the condensate to the outside via the hose.
Control specifications in detail
∙ Condition(s) required to use the mode : The Drain Pump Option is used, or the model name
∙ Drain Pump ON : (Cooling or Auto cooling or Dehumidifying mode ON) and
(Outdoor Comp ON) and (Indoor unit Thermo-ON)
Thermo-ON
Thermo-OFF
Outdoor Comp ON
Outdoor Comp OFF
Detected by the Float S/W
Not detected by the Float S/W
Drain Pump ON
Drain Pump OFF
∙ Drain Pump OFF : (Operation OFF) or (Indoor unit Thermo OFF)
Thermo-ON
Thermo-OFF
Outdoor Comp ON
Outdoor Comp OFF
Detected by the Float S/W
Not detected by the Float S/W
Drain Pump ON
Drain Pump OFF
Notes
The drain pump activates if the Float S/W operates in heating mode
Outdoor Comp ON
Outdoor Comp OFF
Detected by the Float S/W
Not detected by the Float S/W
Drain Pump ON
Drain Pump OFF
Samsung Electronics
(Rem_Opt) is set to 1-Way, 2-Way, or 4-Way
Cooling or Auto cooling or
Dehumidifying mode
Cooling or Auto cooling or
Dehumidifying mode
Cooling or Auto cooling or
Dehumidifying mode
If 3-min delay option (Rem_Opt) is on