Suspension Of Starting By Abnormal Compression Ratio - Samsung AM080FXWANR Service Manual

System air conditioners outdoor unit
Hide thumbs Also See for AM080FXWANR:
Table of Contents

Advertisement

Troubleshooting
4-3 Appropriate Measures for Different Symptom (cont.)
4-3-35

: Suspension of starting by abnormal compression ratio

Outdoor unit
display
Duct, Cassette (1/2 Way),Console, Celing
Operation
Indoorunit
display
×
※ ● : ON ◑ : Flash ×: OFF
Judgment
∙ Compression ratio [(High pressure+1.03)/(Low pressure+1.03)] less than 1.5 and lasts for 10 minutes or more
Method
∙ Differential pressure (high pressure- low pressure) less than 0.4 MPa.g and lasts for 10 minutes or more
∙ Indoor and Outdoor EEV breakdown
∙ 4Way Valve breakdown
Cause of
problem
∙ High and Low pressure sensor defective
∙ Refrigerant shortage
1. Cause of problem
Auto Trial Operation
Is the S-net estimated value
and the Manifold Gauge value in range?
Are the 4Way Valve normally operating?
Are the Indoor Unit and Outdoor Unit EEV
normally operating?
Is current of compressor normally?
Complete
Samsung Electronics
Defrost
Timer
Fan
Filter/MPI
×
Yes
Yes
No
Yes
Cassette (4/Mini4 Way)
Operation Defrost
Timer
×
No
No
No
No
Wall-mounted (NeoForte)
Filter Operation
Timer
Turbo
Replace defective sensor
Replace defective sensor
Check the 4Way Valve
Check the relevant EEV
Compressor Inspection
Check the refrigerant
120

Advertisement

Table of Contents
loading

Table of Contents