Option Setting Error Of Outdoor Unit - Samsung AM080FXWANR Service Manual

System air conditioners outdoor unit
Hide thumbs Also See for AM080FXWANR:
Table of Contents

Advertisement

Troubleshooting
4-3 Appropriate Measures for Different Symptom (cont.)

4-3-48 Option setting error of outdoor unit

Outdoor unit display
Indoorunit display
Judgment Method
Special Cause
1. Cause of problem
Is the Compressor breakdown
setting value is "not set"?
Is the outdoor unit EEPROM accurately
connected to connector?
Download relevant model EEPROM and then reset.
※ Execute automatic commissioning for UP
cancellation after EEPROM download.
Samsung Electronics
(Operation) ×(Reservation)
• Refer to the judgment method below.
• Option setting error of outdoor unit
(There is No Compressor start in a Unit because of Compressor Cut off Option Setting. )
Yes
Yes
(Blast) ×(Filter) ×(Defrost)
Set the compressor breakdown setting
value as "not set"
No
※ When There is No Compressor start in a Unit
because of Compressor Cut off Option
Setting, E560.
No
Connect outdoor unit EEPROM and then reset.
137

Advertisement

Table of Contents
loading

Table of Contents