Samsung AM080FXWANR Service Manual page 233

System air conditioners outdoor unit
Hide thumbs Also See for AM080FXWANR:
Table of Contents

Advertisement

Piping Diagram
7-3 Functions (cont.)
7-3-2 Control (cont.)
7-3-2-5 Protective control (cont.)
- If the compression ratio is low,
1st step Increase of the superheat degree : The superheat degree for compressor suction is increased .
2nd step Increase of the minimum compressor frequency : The minimum compressor frequency is increased to the predefined
3rd step Comp Trip : If in critical state for 10 min, stop the compressors and trigger an error (E428).
Samsung Electronics
model-specific frequency.
232