Outdoor Unit Option Switch Settings - Samsung AM080FXWANR Service Manual

System air conditioners outdoor unit
Hide thumbs Also See for AM080FXWANR:
Table of Contents

Advertisement

Key Options

8-3 Outdoor unit option switch settings

● Setting outdoor unit option switches : A TYPE PBA
K21 K22
※ If you install HR products, you must match the address between the MCU and the indoor unit.
Switch
Setting
SW51/
Setting total number of installed indoor unit
SW52
SW51: Tens digit, SW52: Units digit
ON
H/P(Heat Pump) System
K5
OFF
HR(Heat Recovery) System
Enable maximum capacity restriction for cooling
ON
operation
K6
Disable maximum capacity restriction for cooling
OFF
operation
K7
K8
ON
ON
Outdoor unit address: No 1
ON OFF
Outdoor unit address: No 2
OFF ON
Outdoor unit address: No 3
OFF OFF
Outdoor unit address: No 4
SW57
Setting total number of connected MCU
K21 K22
ON
ON
Water circulation
Anti-freeze circulation
SW58
ON OFF
(freezing point of anti-freeze must be below -8 °C)
Anti-freeze circulation
OFF ON
(freezing point of anti-freeze must be below -15 °C)
※ Maintain appropriate concentration level of anti-freeze according to SW58 switch setting.
Samsung Electronics
Function
Selecting outdoor unit address
Selecting type of circulating water
SW58
K21 K22
TEN
Remarks
Setting can be done from the main outdoor unit only
(sub unit: setting is unnecessary)
Ex) When 12 indoor units are installed
Connect Liguid pipe and High pressure gas pipe
Close outdoor unit's heatpump valve
Restrict excessive capacity increase when operating indoor
units with small capacity
Main unit
Sub unit 1
Sub unit 2
Sub unit 3
Setting can be done from main unit only
Ex) When 3 MCUs are installed
Minimum temperature of entering water -5 °C
Minimum temperature of entering water -10 °C
ONE
MCU
SW51: 1, SW52: 2
-
SW57: 3, SW52: 2
-
261