5.2.10 Trace Memory

TRACE MEMORY
5–14
PATH: SETPOINTS
S1 PQMII SETUP
[ ]
TRACE MEMORY USAGE:
1 x 36 cycles
TRACE MEMORY TRIGGER
MESSAGE
MODE: ONE SHOT
Ia OVERCURRENT TRIG
MESSAGE
LEVEL: OFF % CT
Ib OVERCURRENT TRIG
MESSAGE
LEVEL: OFF % CT
Ic OVERCURRENT TRIG
MESSAGE
LEVEL: OFF % CT
In OVERCURRENT TRIG
MESSAGE
LEVEL: OFF % CT
Va OVERVOLTAGE TRIG
MESSAGE
LEVEL: OFF % NOMINAL
Vb OVERVOLTAGE TRIG
MESSAGE
LEVEL: OFF % NOMINAL
Vc OVERVOLTAGE TRIG
MESSAGE
LEVEL: OFF % NOMINAL
Va UNDERVOLTAGE TRIG
MESSAGE
LEVEL: OFF % NOMINAL
Vb UNDERVOLTAGE TRIG
MESSAGE
LEVEL: OFF % NOMINAL
Vc UNDERVOLTAGE TRIG
MESSAGE
LEVEL: OFF % NOMINAL
SWITCH INPUT A TRIG:
MESSAGE
OFF
SWITCH INPUT B TRIG:
MESSAGE
OFF
SWITCH INPUT C TRIG:
MESSAGE
OFF
SWITCH INPUT D TRIG:
MESSAGE
OFF
TRACE MEMORY TRIGGER
MESSAGE
DELAY: 0 cycles
TRACE MEMORY TRIGGER
MESSAGE
RELAY: OFF
The Trace Memory feature involves a separate sampling data stream. All input channels
are sampled continuously at a rate of 16 times per cycle. Using a single-cycle block
interval, the input samples are checked for trigger conditions as per the trigger setpoints
below. Note that the normal sampling burst (64 samples/cycle, 2 cycles) used for all
CHAPTER 5: SETPOINTS
TRACE MEMORY
Range: 1 x 36, 2 x 18, 3 x 12 cycles
Range: One Shot, Retrigger
Range: 1 to 150% of CT in steps of 1 or
OFF
Range: 1 to 150% of CT in steps of 1 or
OFF
Range: 1 to 150% of CT in steps of 1 or
OFF
Range: 1 to 150% of CT in steps of 1 or
OFF
Range: 20 to 150% of Nominal in steps
of 1 or OFF
Range: 20 to 150% of Nominal in steps
of 1 or OFF
Range: 20 to 150% of Nominal in steps
of 1 or OFF
Range: 20 to 150% of Nominal in steps
of 1 or OFF
Range: 20 to 150% of Nominal in steps
of 1 or OFF
Range: 20 to 150% of Nominal in steps
of 1 or OFF
Range: Off, Open-to-Closed,
Closed-to-Open
Range: Off, Open-to-Closed,
Closed-to-Open
Range: Off, Open-to-Closed,
Closed-to-Open
Range: Off, Open-to-Closed,
Closed-to-Open
Range: 0 to 30 cycles in steps of 2
Range: Off, Aux1, Aux2, Aux3, Alarm
PQMII POWER QUALITY METER – INSTRUCTION MANUAL