GE PQMII Instruction Manual page 200

Power quality meter
Table of Contents

Advertisement

A–2
STEP 2 DROPOUT ≤
MESSAGE
0.0 kvar
STEP 2 PICKUP
MESSAGE
DELAY: 1.0 min
STEP 2 DISABLE
MESSAGE
TIME: 5.0 min
STEP 3 RELAY:
MESSAGE
OFF
STEP 3 PICKUP ≥
MESSAGE
+600 kvar
STEP 3 DROPOUT ≤
MESSAGE
0.0 kvar
STEP 3 PICKUP
MESSAGE
DELAY: 1.0 min
STEP 3 DISABLE
MESSAGE
TIME: 5.0 min
STEP 4 RELAY:
MESSAGE
OFF
STEP 4 PICKUP ≥
MESSAGE
+600 kvar
STEP 4 DROPOUT ≤
MESSAGE
0.0 kvar
STEP 4 PICKUP
MESSAGE
DELAY: 1.0 min
STEP 4 DISABLE
MESSAGE
TIME: 5.0 min
SYSTEM STABILIZATION
MESSAGE
TIME: 5.0 min
LOW VOLTAGE LEVEL:
MESSAGE
100 V
LOW VOLTAGE DETECT
MESSAGE
DELAY: 1.0 s
STEP PRIORITY:
MESSAGE
1, 2, 3, 4
STEP 1(4) RELAY: The state of the output relay assigned in this message will be
controlled by the
STEP
step, it will not activate upon any other PQMII conditions (i.e. pulse output, alarm, etc.).
If a particular relay has not been assigned to any
PQMII implementation.
STEP 1(4) PICKUP: When the three-phase kvar value is positive and it becomes equal
to or exceeds the value set in this setpoint the output relay assigned to the
energize providing the conditions in all other setpoints are met.
it is assigned to. Once a relay has been assigned to a particular
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
APPENDIX A
Range: –3250.0 to 3250.0 kvar in steps
of 0.1
Range: 0.1 to 60.0 min in steps of 0.1
Range: 0.1 to 60.0 min in steps of 0.1
Range: Alarm, Aux1, Aux2, Aux3, Off
Range: 0.1 to 6500.0 kvar in steps of
0.1
Range: –3250.0 to 3250.0 kvar in steps
of 0.1
Range: 0.1 to 60.0 min in steps of 0.1
Range: 0.1 to 60.0 min in steps of 0.1
Range: Alarm, Aux1, Aux2, Aux3, Off
Range: 0.1 to 6500.0 kvar in steps of
0.1
Range: –3250.0 to 3250.0 kvar in steps
of 0.1
Range: 0.1 to 60.0 min in steps of 0.1
Range: 0.1 to 60.0 min in steps of 0.1
Range: 0.1 to 60.0 min in steps of 0.1
Range: 30 to 65000 V in steps of 10 or
OFF
Range: 0.5 to 600.0 s in steps of 0.5
Range: 24 combinations
, it will function as per standard
STEP
STEP
will

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pqm ii